# DIPOL.db: EPICS records generated from the DCS_REQ DB entries on 30-07-2010 # From http://panda-controls.gsi.de/DB/interactiveTable.php?name=ProcessVariables&keephidden=0664&showonly=5 # This is an autogenerated draft, doublecheck it before use (and remove this line)! record(ai, "PANDA:DIPOL:COIL:C1:T_R"){ field(DESC, "Dipole coil temperature (1)") field(EGU, "C") field(PREC, "3") field(SCAN, "1 second") field(VAL, "35") field(HIHI, "50") field(HIGH, "40") field(LOLO, "10") field(LOW, "15") field(HOPR, "60") } record(ai, "PANDA:DIPOL:COIL:C2:T_R"){ field(DESC, "Dipole coil temperature (2)") field(EGU, "C") field(PREC, "3") field(SCAN, "1 second") field(VAL, "35") field(HIHI, "50") field(HIGH, "40") field(LOLO, "10") field(LOW, "15") field(HOPR, "60") } record(ai, "PANDA:DIPOL:COIL:C3:T_R"){ field(DESC, "Dipole coil temperature (3)") field(EGU, "C") field(PREC, "3") field(SCAN, "1 second") field(VAL, "35") field(HIHI, "50") field(HIGH, "40") field(LOLO, "10") field(LOW, "15") field(HOPR, "60") } record(ai, "PANDA:DIPOL:COIL:C4:T_R"){ field(DESC, "Dipole coil temperature (4)") field(EGU, "C") field(PREC, "3") field(SCAN, "1 second") field(VAL, "35") field(HIHI, "50") field(HIGH, "40") field(LOLO, "10") field(LOW, "15") field(HOPR, "60") } record(ai, "PANDA:DIPOL:COOL:P_F"){ field(DESC, "Cooling water pressure") field(EGU, "kPa") field(PREC, "3") field(SCAN, "1 second") field(VAL, "400") field(HIHI, "800") field(HIGH, "600") field(LOLO, "200") field(LOW, "300") field(HOPR, "800") field(LOPR, "200") } record(ai, "PANDA:DIPOL:COOL:C1:T_F"){ field(DESC, "Cooling water temprature (1)") field(EGU, "C") field(PREC, "1") field(SCAN, "1 second") field(VAL, "25") field(HIHI, "35") field(HIGH, "30") field(LOLO, "15") field(LOW, "20") field(HOPR, "85") field(LOPR, "10") } record(ai, "PANDA:DIPOL:COOL:C2:T_F"){ field(DESC, "Cooling water temprature (2)") field(EGU, "C") field(PREC, "1") field(SCAN, "1 second") field(VAL, "25") field(HIHI, "35") field(HIGH, "30") field(LOLO, "15") field(LOW, "20") field(HOPR, "85") field(LOPR, "10") } record(ai, "PANDA:DIPOL:COOL:H2O_Flow"){ field(DESC, "Cooling water flow") field(EGU, "l/s") field(PREC, "3") field(SCAN, "1 second") field(VAL, "4") field(HIHI, "6") field(HIGH, "5") field(LOLO, "3") field(LOW, "3.5") field(HOPR, "6") field(LOPR, "2") } record(ai, "PANDA:DIPOL:COIL:I_c"){ field(DESC, "Dipole coil current") field(EGU, "A") field(PREC, "3") field(SCAN, "10 second") field(VAL, "1500") field(HIHI, "1500.05") field(HIGH, "1500.02") field(LOLO, "1499.95") field(LOW, "1499.98") field(HOPR, "1800") field(LOPR, "100") } record(ai, "PANDA:DIPOL:C1:B"){ field(DESC, "Magnetic field intensity (1)") field(EGU, "T") field(PREC, "4") field(SCAN, "1 second") field(VAL, "1") field(HOPR, "1.02") field(LOPR, "0.98") } record(ai, "PANDA:DIPOL:C2:B"){ field(DESC, "Magnetic field intensity (2)") field(EGU, "T") field(PREC, "4") field(SCAN, "1 second") field(VAL, "1") field(HOPR, "1.02") field(LOPR, "0.98") }