Difference: ForwardEndcapRacks (1 vs. 3)

Revision 3
15 Feb 2016 - Main.FritzHerbertHeinsius
Line: 1 to 1
 
META TOPICPARENT name="ForwardEndcapEMC"

Racks close to detector

  • Rack for forward endcap EMC on left side target spectrometer:
Line: 7 to 7
 
  • Rack for forward endcap EMC on right side of target spectrometer:
    target_spektrometer_right.jpg
Changed:
<
<
  • HV patch panel
>
>

HV patch panel

 

Towards magnet front solenoid ducts:
Changed:
<
<
980 times Huber+Suhner Enviroflex coaxial cable, Outer diameter 1.8 mm, Total cross section 52 cm^2
>
>
980 times Huber+Suhner Enviroflex_178 coaxial cable, Outer diameter 1.8 mm, Total cross section 52 cm^2 http://www.hubersuhner.com/ProdDet/4503104

Voltages: 1000 V and less than 500 V.

Size of patch panel: tbd.
 

Routed to service area E10: 1000 coaxial cables. Total cross section 400 cm^2
Changed:
<
<
  • LV for preamplifier
Wiener PL512, 230 V 3.6 kW
>
>

LV for preamplifier

Wiener PL512, 230 V 3.6 kW (PBN512 - 3U RASO 19“ power bin for rack mounting, PBX512 - EX Power Box with Display, 6 x MDH 2-8 V dual power modules +/-30A per channel)
 

Towards magnet/detector:
Added:
>
>
  54 (?) times Ölfeld FD90CY 0026651 superfine copper-strand, Outer diameter 9.7 mm, Total cross section: 82 cm^2
Changed:
<
<
  • LV for SADCs
>
>
Voltages: +6V, GND, -6V, GND.

LV for SADCs

 

2 Crates Wiener PL508, 230 V 10 kW each, one with 12 V 8 channels and second 12 V 3 channels.

Towards magnet/detector: 22 (?) times Ölfeld (?), Outer diameter 17.1 mm, Total cross section: 102 cm^2
Changed:
<
<
  • LV for THMP and lightpulser
>
>

LV for THMP and lightpulser

tbd.

Optical links (SADCs)

Patch panel? 496 fires, 2mm? directly routed to E10?
 
Changed:
<
<
  • Optical links
>
>

DCS can bus, ethernet

 
Changed:
<
<
496 fibres, 2mm?
  • DCS canbus, ethernet
>
>
tbd.
 

  • Questions to be answered:
Any info about the characteristics of your electronics system (crates, boards, controllers, power supplys) these racks must host is useful. In particular, power requirements, operational voltages and currents, number of units, any cooling requirements, any other requirements.
Line: 38 to 51
 

Racks in services

Changed:
<
<
7 ISEG HV ECH33/44 each 8U
>
>
7 ISEG HV ECH33/44 (?) each 8U
 

-- FritzHerbertHeinsius - 01 Feb 2016
Revision 2
02 Feb 2016 - Main.FritzHerbertHeinsius
Line: 1 to 1
 
META TOPICPARENT name="ForwardEndcapEMC"

Racks close to detector

Added:
>
>
  • Rack for forward endcap EMC on left side target spectrometer:
    target_spektrometer_left.jpg

  • Rack for forward endcap EMC on right side of target spectrometer:
    target_spektrometer_right.jpg
 

  • HV patch panel
Line: 12 to 17
  Wiener PL512, 230 V 3.6 kW

Towards magnet/detector:
Changed:
<
<
 54 (?) times Ölfeld FD90CY 0026651 superfine copper-strand, Outer diameter 9.7 mm, Total cross section: 82 cm^2
>
>
54 (?) times Ölfeld FD90CY 0026651 superfine copper-strand, Outer diameter 9.7 mm, Total cross section: 82 cm^2
 

  • LV for SADCs
Line: 36 to 41
  7 ISEG HV ECH33/44 each 8U

-- FritzHerbertHeinsius - 01 Feb 2016
Added:
>
>

META FILEATTACHMENT attachment="target_spektrometer_left.jpg" attr="" comment="Rack for forward endcap EMC on left side target spectrometer" date="1454428481" name="target_spektrometer_left.jpg" path="target_spektrometer_left.jpg" size="2242583" user="FritzHerbertHeinsius" version="1"
META FILEATTACHMENT attachment="target_spektrometer_right.jpg" attr="" comment="Rack for forward endcap EMC on right side of target spectrometer" date="1454428765" name="target_spektrometer_right.jpg" path="target_spektrometer_right.jpg" size="2329608" user="FritzHerbertHeinsius" version="1"
 
This site is powered by FoswikiCopyright © by the contributing authors. All material on this collaboration platform is the property of the contributing authors.
Ideas, requests, problems regarding PANDA Wiki? Send feedback
Imprint (in German)